Wiring
Wire size and voltage drop
Undersized cable runs hot and starves the load. Set the amps and the run, and get the gauge, the voltage at the far end, and the fuse.
Updates as you typeSame math as the original Megawatt tool
Use this wire
Within limitsCopper area to scale. Dashed ring is 4/0 AWG.
Gauge
6 AWG
Fuse
0A
At the load
0V
0
Voltage drop
0V
Derated ampacity
0A
Drop as the run gets longer
Drop with the chosen gaugeYour limitYour run
Every gauge, checked
How the math works
Required copper area is CM = 10.75 × amps × one-way feet × 2 ÷ allowed drop volts, using the published Megawatt table for 105°C copper. The wire must also carry the current after derating: 85% in an engine bay, and 70%, 60%, 50%, or 40% as more wires share a bundle. The fuse floor is 125% of the load, stepped up to a standard size, and capped at the wire’s derated ampacity.
Keep planning
Solar plannerRoof layout, three build tiers, parts listsBattery bankDaily loads, days off-grid, and solar in. Voltage, amp-hours, and the Vatrer battery out.Solar arrayWatt-hours and sun hours in. Minimum array and pack counts out.Solar by location and seasonZIP and panel watts in. Twelve months of real watt-hours out.